Description
Standards
National : NF C 33-226; NF C 33-226Description
Usage
NF C 33-226 cables are the new generation of cables for public power distribution network 12/20 kV.
Design
The cable is made of 3 bunched cores with a messenger.
Aluminium screen is made to ground short-circuit currents of EdF network, up to 1000 A for 1 s. for underground networks.
Electrical caracteristics
Calculated from IEC 60949, Permissible short circuit current is applicable for the conductor during 1s.
Marking
Example NEXANS - plant number- BGN5 NF C 33226 int. designation- section - Al - 12/20 (24) kV - year - month - installation guide type - G sheath thickness - SC semi-conductor thickness - EC screen thickness - C2 RT- installation temperature - Eca
Core identification: 1, 2, 3 helix-wise.
The marking is metric over one core sheath, as well as a tracing mark.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum |
Insulation | XLPE (chemical) |
Outer sheath | PE-HD |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 12 / 20 (24) kV |
Mechanical characteristics | |
Cable flexibility | Rigid |
Usage characteristics | |
Flame retardant | C2, NF C 32-070 |
Products and services
Docs and info
Selling information
Options
NF C 33-226 cables can be manufactured with the following options:
- Copper conductor
- Other voltage
- Other section
- Grounding conductor
- Thicker aluminium screen
- Bunch + fibre optic element.